Description

Overview

The ARI FABA®-Plus Fig. 22.046 (from manufacturer datasheet 040005, Edition 04/16) is a stop valve with bellows seal, straight through with flanges. The body material is EN-JS1049 (EN-GJS-400-18U-LT) spheroidal graphite iron, nominal pressure PN16, nominal size range DN15–DN350.

Fig. 22.046 belongs to the FABA®-Plus 046 (straight through with flanges) series; the same datasheet also covers Fig. 12.046 (PN16, EN-JL1040), Fig. 23.046 (PN25), Fig. 34.046 (PN25, cast steel) and Fig. 35.046 (PN40, cast steel). The data on this page refers to Fig. 22.046; shared tables are reproduced as printed in the datasheet.

Certifications and tests (from the datasheet):

  • DIN DVGW type approval (EN-JS1049)
  • EN ISO 15848-1 / TA - Luft low-emission certification, TÜV test no. TA 07 2016 C04
  • TRB 801 Annex II No. 45 production allowance (except EN-JL1040)
  • DIN DVGW-Reg. NG-4313AO 0772
  • Standards applied: EN 13789 (EN-JL1040, EN-JS1049)

Features

  • Double wall bellows seal as standard
  • Plug with marginal seat
  • Stem with fine thread
  • Flat lubricating nipple
  • Locking device, countersunk
  • Cast iron variations with nodular iron bonnet as standard
  • Heat dissipating bonnet
  • Bonnet optimised for accessories
  • Secondary sealing: gland packing
  • Position indicator as standard
  • Non-rising handwheel
  • Non-rotation lock for each nominal diameter
  • External stem thread
  • Stem with roll hardened thread

Technical data

  • Type: bellows sealed stop valve, straight through, flanged
  • Figure: Fig. 22.046
  • Nominal pressure: PN16
  • Nominal size: DN15–DN350
  • Body material: EN-JS1049 / EN-GJS-400-18U-LT (spheroidal graphite iron)
  • Bonnet material: EN-JS1049 / EN-GJS-400-18U-LT (spheroidal graphite iron)
  • Face-to-face dimension: FTF series 1 acc. to DIN EN 558
  • Standard flanges: acc. to DIN EN 1092-1/-2
  • Operating temperature: -60 °C to 350 °C (below -10 °C on request, see pressure-temperature ratings)
  • Tests/approvals: EN ISO 15848-1 / TA - Luft (TÜV-Test-No. TA 07 2016 C04); DIN DVGW-Reg. NG-4313AO 0772

Parts

Datasheet page 2, table reproduced in full (applies to the 046 straight-through flanged series; Fig. 22.046 corresponds to the “Fig. 22. / 23.046” column):

Pos.Sp.p.DescriptionFig. 12.046Fig. 22. / 23.046Fig. 34. / 35.046
1BodyEN-JL1040, EN-GJL-250EN-JS1049, EN-GJS-400-18U-LTGP240GH+N, 1.0619+N
1.2Seat ringX20Cr13+QT, 1.4021+QT≤DN50: X20Cr13+QT, 1.4021+QT / ≥DN65: G19 9 NbSi, 1.4551same
2BonnetEN-JS1049, EN-GJS-400-18U-LTEN-JS1049, EN-GJS-400-18U-LTGP240GH+N, 1.0619+N
3xPlug≤DN200: X20Cr13+QT, 1.4021+QT (hardened) / ≥DN250: P265GH, 1.0425 / Stellit 21samesame
4xSpindle unit—samesame
4.1Bellows sealX6CrNiMoTi17 12 2, 1.4571samesame
4.2StemX20Cr13+QT, 1.4021+QTsamesame
5Handwheel≤DN125: St (cataphoretic coating) / ≥DN150: EN-JL1040, EN-GJL-250 (epoxy-coating)samesame
6xPacking ringPure graphitesamesame
7Hexagon bolt5.6—same
7Stud—25CrMo4, 1.7218same
8Hexagon nut—C35E, 1.1181same
9xGasketPure graphite (CrNi laminated with graphite)samesame
15xInsert nuts11SMn30+C, 1.0715+Csamesame
└Spare parts

Pressure-temperature-ratings

Datasheet page 14, tables reproduced in full. Intermediate values for max. permissible operational pressures can be determined by linear interpolation of the given temperature/pressure chart.

Acc. to DIN EN 1092-2:

MaterialNominal pressure-60 °C to <-10 °C¹)-10 °C to 120 °C150 °C200 °C250 °C300 °C350 °C400 °C450 °C
EN-JL104016 (bar)—1614,412,811,29,6———
EN-JS104916 (bar)on request1615,514,713,912,811,2——
EN-JS104925 (bar)on request2524,32321,82017,5——
EN-JS104940 (bar)on request4038,836,834,83228——

Acc. to manufacturer’s standard:

MaterialNominal pressure-60 °C to <-10 °C¹)-10 °C to 120 °C150 °C200 °C250 °C300 °C350 °C400 °C450 °C
1.0619+N25 (bar)18,72523,9222017,21614,88,2
1.0619+N40 (bar)304038,135322825,723,813,1
1.046025 (bar)18,72523,9222017,21614,810
1.046040 (bar)304038,135322825,723,816

Acc. to DIN EN 1092-1:

MaterialNominal pressure-60 °C to <-10 °C¹)-10 °C to 100 °C150 °C200 °C250 °C300 °C350 °C400 °C450 °C
1.440816 (bar)161614,513,412,711,811,410,9—
1.440825 (bar)252522,72119,818,517,817,1—
1.440840 (bar)404036,333,731,829,728,527,4—
1.458116 (bar)81615,614,914,113,312,812,4—
1.458125 (bar)12,52524,523,322,120,820,119,5—
1.458140 (bar)204039,237,335,433,332,131,2—

¹) Studs and nuts made of A4-70 (at temperatures below -10 °C).

Dimensions and weights

Datasheet page 2, table reproduced in full (046 straight-through flanged series, DN15–DN400; Fig. 22.046 supply range DN15–DN350):

ItemDN15DN20DN25DN32DN40DN50DN65DN80DN100DN125DN150DN200DN250DN300DN350DN400
Face-to-face dimension L (mm), FTF series 1 acc. to DIN EN 5581301501601802002302903103504004806007308509801100
H1 (mm)2052052102102252302452653653954305507207759751015
ØC, PN16 (mm)125125125125150150175175225300400520520520640640
ØC, PN25 (mm)125125125125150150175175300300400520520520640640
ØC, PN40 (mm)125125125125150150175225300300400520520———
Travel (mm)66881313162025324050708090100
Kvs-value (m³/h)5,37,2121628,543751051702704056751090146020102640
Zeta-value—2,94,94,36,555,45,15,95,55,34,95,65,26,15,9
Weights 12. / 22. / 23.046 (kg)3,74,55,66,98,91115,321,132,451,674147247404524—
Weights 34.046 (kg)——————————168268395629865—
Weights 35.046 (kg)4,15,16,27,310,612,619,126,13560,388160310———

Note: range of tolerance for Kvs-values acc. to VDI/VDE 2173.

Standard-flange dimensions (DIN EN 1092-1/-2, PN16 rows, datasheet page 14; flange holes/thickness tol. acc. to DIN 2533/2544/2545):

PN16DN15DN20DN25DN32DN40DN50DN65DN80DN100DN125DN150DN200DN250DN300DN350DN400
ØD (mm)95105115140150165185200220250285340405460520580
ØK (mm)657585100110125145160180210240295355410470525
n x Ød (mm)4x144x144x144x184x184x184x18¹)8x188x188x188x2212x2212x2612x2616x2616x30

¹) DN80 also possible with 8 bore holes acc. to DIN EN 1092-1/-2.

Plug design and differential pressure limits

Plug designs listed in the datasheet: isolation plug with marginal seat (stellited seat and plug available), soft-seal plug (PTFE + 25 % carbon, max. operating temperature 200 °C), screw-down non-return plug with re-setting spring, regulating plug with marginal seat, regulating plug with soft seal, screw-down non-return regulating plug, balancing plug (standard: DN15–300 with marginal seat, from DN350 with flat seat).

At differential pressures exceeding the values below, a pressure balancing plug is required:

DN125150200250300350400500
Gauge press. ΔP (bar)252114964,53,51,5

Valves with balancing plugs must be installed with the medium flowing over the plug as indicated by the flow direction arrow on the valve body; balancing plugs are fully effective only in closed systems; a bypass line is necessary if pressure equalization takes too long owing to the volume of the piping system.

Accessories

Accessories listed on datasheet page 13: limit switch, hood valve acc. to DIN EN 12828 (tamper-resistant handwheel cover), chain wheel, stem extension (please specify height in your order), lubricating nipple / locking device / travel limiter (accessories are not included in standard supply).

Ordering information

Please indicate when ordering: Figure-No., nominal pressure, nominal diameter, special design/accessories (datasheet example: Figure 35.046, PN40, DN100).

For a quotation on the ARI FABA®-Plus Fig. 22.046, please send the figure no. (22.046), DN, PN and quantity.