Description
Overview
The ARI-PREDU® Fig. 22.701 (from manufacturer datasheet 700001, Edition 08/19) is a self-operated pressure regulating valve, straight through with diaphragm actuator DMA. It is a direct acting proportional regulator: the downstream pressure is regulated — the valve closes when the downstream pressure rises — without any external energy supply. The Fig. 22.701 body is EN-JS1049 spheroidal graphite iron, PN16, DN15–DN150, downstream pressure ranges 0.2–16 barg.
The same datasheet covers Fig. 12.701 (PN16, EN-JL1040), Fig. 23.701 (PN25), Fig. 34.701 (PN25, 1.0619+N), Fig. 35.701 (PN40, 1.0619+N) and Fig. 62.701/65.701 (PN16/PN40, 1.4581 stainless steel). The data on this page refers to Fig. 22.701.
Features
- Compact design, construction without pillars
- Exact and easy adjustment, diameter-independent ranges
- Simple change of spring and actuator; 5 exchangeable actuator sizes (DMA 40/80/160/250/400), 3 exchangeable spring sizes
- Pressure balanced by stainless steel bellows
- Spindle sealing via stainless steel bellows
- Tapered seat ring, screwed seat ring
- Kvs values reduceable (reduced Kvs 0.1–6.3 m³/h on small sizes)
- Flow divider for noise reduction (optional), plug with PTFE soft seal (optional)
Technical data
- Type: self-operated pressure regulating valve (pressure reducing valve), straight through, with diaphragm actuator DMA
- Figure: Fig. 22.701
- Nominal pressure: PN16
- Nominal size: DN15–DN150
- Body material: EN-JS1049 / EN-GJS-400-18U-LT
- Downstream pressure ranges: 0.2–16 barg (actuator/spring combination dependent)
- Operating fields: fluids of group II acc. to Pressure Equipment Directive 2014/68/EU — steam, neutral gases, vapours and liquids
- Face-to-face dimension: FTF series 1 acc. to DIN EN 558
- Standard flanges: acc. to DIN EN 1092-1/-2
- Leakage class: I acc. to DIN EN 1349 / DIN EN 60534-4 (≤ 0.05 % of Kvs value)
Kvs values
Datasheet p3:
| DN | 15 | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Kvs standard (m³/h) | 3,2 | 5 | 8 | 12,5 | 20 | 32 | 50 | 80 | 125 | 190 | 280 |
| Kvs reduced (m³/h) | 0,1/0,4/1/2,5 | 0,1/0,4/1/2,5/4 | 0,1/0,4/1/2,5/4/6,3 | — | — | — | — | — | — | — | — |
Dimensions
Face-to-face dimension L, FTF series 1 acc. to DIN EN 558 (datasheet p3):
| DN | 15 | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| L (mm) | 130 | 150 | 160 | 180 | 200 | 230 | 290 | 310 | 350 | 400 | 480 |
| Max. diff. pressure drop (bar) | 40 | 40 | 25 | 25 | 25 | 25 | 20 | 20 | 20 | 16 | 16 |
Valve height H depends on the actuator: e.g. DN15 DMA 400: 495 mm, DMA 40: 435 mm; DN150 DMA 400: 690 mm (datasheet p3). Proportional band and spring ranges per actuator/DN combination are tabulated on datasheet page 3 (e.g. DMA 400, downstream range 0.2–0.6 barg, proportional band 0.05–0.15 bar depending on DN).
Installation notes
With steam and liquids hotter than the allowable actuator working temperature, a water seal pot must be installed in the control line to protect the diaphragm (datasheet p4). The datasheet system drawing shows the recommended station layout: separator, strainer (fine screen), flow indicator, upstream/downstream manometers, bypass pipe, condensate traps (CONA S / CONA B) and 10 × DN (min. 1 m) straight inlet.
Ordering information
Please indicate when ordering: figure no. (22.701), DN, PN, downstream pressure set range, spring/actuator size (DMA …) and medium.
For a quotation on the ARI-PREDU® Fig. 22.701, please send the medium, inlet pressure, required outlet pressure and flow rate.