ARI CONA®B Fig. 45.600 / 45.601 (from manufacturer datasheet 600001, Edition 05/20, AWH Armaturen-Werk Halle GmbH, a member of the ARI group) is a thermostatic bimetallic steam trap in PN40, nominal size range DN15–DN25. Fig. 600…1 is supplied with inside strainer; Fig. 601…1 (Y) with outside strainer.
The PN40 group is available in three body materials: forged steel 1.0460 (Fig. 45.600 / 45.601), high temperature steel 16Mo3 (Fig. 85.600 / 85.601) and stainless steel 1.4541 (Fig. 55.600 / 55.601). This page covers Fig. 45.600 / 45.601; shared tables are reproduced as printed in the datasheet. For ANSI versions refer to data sheet CONA®B-ANSI.
Features
- Thermostatic steam trap with non-corrosive and robust water hammer proof bimetallic controller
- Automatic air-venting during start up and operation of the plant
- Check valve
- With inside strainer (Fig. 600) or outside strainer (Fig. 601 Y)
- Installation in any position, except screw cap downwards
- Subcooling of condensate is continuously adjustable (observe the operation instructions)
- Maintenance simplified due to screwed cap without sealing
Controller (chooseable for operating range):
- Controller R13: up to inlet pressure 13 bar
- Controller R22: up to inlet pressure 22 bar
- Controller R32: up to inlet pressure 32 bar
Options:
- Outside strainer with blow down valve (Pos. 46)
- Ball valve for blow down (Pos. 56) with internal strainer (observe operating and installation instructions)
Technical data
- Type: thermostatic bimetallic steam trap
- Figures: Fig. 45.600 / 45.601 (Y)
- Nominal pressure: PN40
- Nominal size: DN15–DN25 / NPS 1/2”–1”
- Body material: P250 GH, 1.0460 (forged steel)
- Operating pressure PS: 32 barg at 250 °C / 22 barg at 385 °C / 14,5 barg at 450 °C
- Allowable differential pressure ΔPMX for controllers: 32 bar (R32) / 22 bar (R22) / 13 bar (R13)
- Types of connection: flanges …1 acc. to DIN EN 1092-1; screwed sockets …2 (Rp acc. to DIN EN 10226-1 or NPT acc. to ANSI B1.20.1); socket weld ends …3 acc. to DIN EN 12760; butt weld ends …4 (weld preparation acc. to EN ISO 9692, identification No. 1.3 and 1.5)
Parts
Datasheet page 5, table reproduced in full (PN40 group):
| Pos. | Sp.p. | Description | Fig. 45.600 / 45.601 | Fig. 85.600 / 85.601 | Fig. 55.600 / 55.601 |
|---|---|---|---|---|---|
| 1 | Body | P250 GH, 1.0460 | 16Mo3, 1.5415 | X6CrNiTi18-10, 1.4541 | |
| 2 | x | Strainer | X5CrNi18-10, 1.4301 | same | same |
| 6 | Cap | P250 GH, 1.0460 | 16Mo3, 1.5415 | X6CrNiTi18-10, 1.4541 | |
| 7 | x | Strainer | X5CrNi18-10, 1.4301 | same | same |
| 8 | x | Strainer plug | X6CrNiTi18-10, 1.4541 | same | same |
| 24 | x | Controller, cpl. | TB 102 / 85 (corrosion resistant bimetal) | same | same |
| 46 | x | Blow down valve, cpl. | X6CrNiTi18-10, 1.4541 | same | same |
| 56 | x | Ball valve for blow down (G 3/8”) | GX5CrNiMo19-11-2, 1.4408 | same | same |
Dimensions and weights
Datasheet page 5, table reproduced in full (PN40, DN15–DN25):
| Item | DN15 flanges | DN20 flanges | DN25 flanges | DN15 screwed sockets | DN20 screwed sockets | DN25 screwed sockets | DN15 socket weld | DN20 socket weld | DN25 socket weld | DN15 butt weld | DN20 butt weld | DN25 butt weld |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NPS | 1/2” | 3/4” | 1” | 1/2” | 3/4” | 1” | 1/2” | 3/4” | 1” | 1/2” | 3/4” | 1” |
| L (mm) | 150 | 150 | 160 | 95 | 95 | 95 | 250 | 250 | 250 | 250 | 250 | 250 |
| H (mm) | 98 | 98 | 98 | 98 | 98 | 103 | 98 | 98 | 98 | 98 | 98 | 98 |
| H1 (mm) | 62 | 62 | 62 | 62 | 62 | 55 | 62 | 62 | 62 | 62 | 62 | 62 |
| S (mm) | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 |
| S1 (mm) | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| HEX (mm) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| Weight Fig. 600/601 (approx.) (kg) | 3,2 | 3,7 | 4,2 | 1,7 | 1,6 | 2,1 | 2,2 | 2,3 | 2,4 | 2,2 | 2,3 | 2,4 |
Capacity chart
The capacity chart shows the maximum capacity at factory setting. (Other factory-settings for the sub-cooling on request.)
- Curve 1: Maximum flow of hot condensate at approx. 10 K below saturation temperature.
- Curve 2: Maximum flow of sub-cooled condensate at approx. 30 K below saturation temperature (with back-up of condensate).
- Curve 3: Maximum flow at cold condensate at about 20 °C (during start-up of a cold installation).
The condensate temperature determines the opening of the controller. Capacity is increased with the sub-cooling temperature of the condensate.
Ordering information
Please indicate when ordering: Figure-No. (45.600 or 45.601), nominal pressure (PN40), nominal diameter, controller range (R13/R22/R32), type of connection.
For a quotation on the ARI CONA®B Fig. 45.600 / 45.601, please send the figure no., DN, PN and quantity.