Description

Overview

ARI CONA® S Fig. 630 is a ball float steam trap with level control for the drainage of water from compressed air and gas systems, PN16/PN40, DN15-DN100, offered with flanges (Fig. 630…1), screwed sockets (Fig. 630…2), socket weld ends (Fig. 630…3) or butt weld ends (Fig. 630…4). Body and hood materials follow the Fig. selection: grey cast iron EN-JL1040, SG iron EN-JS1049, forged steel/cast steel 1.0460 with 1.0619+N hood, stainless steel 1.4541 with 1.4308 hood, or low temperature steel 1.0571 with 1.6220+QT hood. Discharge is continuous, and the discharged volume is adjusted immediately via the liquid level in the valve and the float.

Features

  • Ball float steam trap with level control for the condensate discharge from compressed air and gas systems, acc. to PED 2014/68/EU fluid group 2, other fluid groups on request
  • Inside strainer and body with flanged hood
  • Non return protection
  • Union (Pos. 52) for recovery pipe, for connecting pipes with outside diameter 8 x 1 mm acc. to EN 10305-4 steel or EN 10216-5 stainless steel, compression type fitting acc. to DIN 2353
  • The controller can be replaced without removing the trap body from the pipework
  • Options: air vent (Pos. 51) or blow down valve (Pos. 46), manual operated
  • Mounting position standard: vertical; optional: horizontal with inlet from right or left (must be indicated when ordering)

Technical Data

FigureNominal pressureMaterialNominal diameter / NPSmax. allowable pressure PMATSminTMAallowable differential pressure ΔPMXfor controller
12.630PN16Body/Hood: EN-JL104015 - 50 / 1/2” - 2”16 bar-10 °C300 °C2 barR2
12.630PN16Body/Hood: EN-JL104015 - 50 / 1/2” - 2”16 bar-10 °C300 °C4 barR4
12.630PN16Body/Hood: EN-JL104015 - 50 / 1/2” - 2”16 bar-10 °C300 °C8 barR8
12.630PN16Body/Hood: EN-JL104015 - 50 / 1/2” - 2”16 bar-10 °C300 °C13 barR13
25.630PN40Body/Hood: EN-JS104915 - 50 / 1/2” - 2”40 bar-10 °C350 °C2 barR2
25.630PN40Body/Hood: EN-JS104915 - 50 / 1/2” - 2”40 bar-10 °C350 °C4 barR4
25.630PN40Body/Hood: EN-JS104915 - 50 / 1/2” - 2”40 bar-10 °C350 °C8 barR8
25.630PN40Body/Hood: EN-JS104915 - 50 / 1/2” - 2”40 bar-10 °C350 °C13 barR13
25.630PN40Body/Hood: EN-JS104915 - 50 / 1/2” - 2”40 bar-10 °C350 °C22 barR22
25.630PN40Body/Hood: EN-JS104915 - 50 / 1/2” - 2”40 bar-10 °C350 °C32 barR32
45.630PN40Body: 1.0460 / Hood: 1.0619+N15 - 100 / 1/2” - 4”40 bar-10 °C400 °C8 barR8
55.630PN40Body: 1.4541 / Hood: 1.430815 - 100 / 1/2” - 4”40 bar-60 °C300 °C13 barR13
55.630PN40Body: 1.4541 / Hood: 1.430815 - 100 / 1/2” - 4”40 bar-60 °C300 °C22 barR22
85.630PN40Body: 1.0571 / Hood: 1.6220+QT15 - 50 / 1/2” - 4”40 bar-50 °C300 °C32 barR32

For versions rated to Class 150 and Class 300 refer to data sheet CONA®S-ANSI. Types of connection:

  • Flanges …1: acc. to DIN EN 1092-2 (EN-JL1040, EN-JS1049) and DIN EN 1092-1 (1.0460, 1.4541, 1.0571)
  • Screwed sockets …2: Rp thread acc. to DIN EN 10226-1 or NPT thread acc. to ANSI B1.20.1
  • Socket weld ends …3: acc. to DIN EN 12760
  • Butt weld ends …4: with joint preparation type acc. to EN ISO 9692 No. 1.3 and 1.5 (note restriction on operating pressure / inlet temperature depending on design)

Pressure-Temperature Ratings

The PMA, TSmin, TMA and allowable differential pressure ΔPMX values per figure and controller are listed in the Technical Data table above. The capacity chart shows the maximum flow quantities of hot condensate for the different controllers and steam trap sizes, differential pressure considering drainage into atmosphere: PN16 standard controller R13, DN15-DN50; PN40 standard controller R22, DN15-DN50; special execution controllers R2, R4, R8, DN15-DN20 and DN25. The maximum flow quantity of cold condensate at about 20 °C is determined by multiplying the appropriate factor F with the hot condensate quantity from the capacity chart.

Dimensions and Weights

Connection dimensions, flanges DN15-DN100 (65-100 flanged only in steel bodies; 65 2), 80 2), 100 2) not available in screwed sockets / socket weld / butt weld):

DN (mm)152025405065 2)80 2)100 2)
NPS (inch)1/2”3/4”1”1 1/2”2”2 1/2”3”4”

Face-to-face acc. to data sheet resp. customer request:

L (mm)DN15DN20DN25DN40DN50DN65DN80DN100
L (EN-JL1040), flanged150150160230230———
L (EN-JS1049), flanged150150160230230———
L (1.0460, 1.4541, 1.0571), flanged150150160230230290310350
L (1.0460, 1.4541, 1.0571), screwed sockets150150160210210———
L (1.0460, 1.4541, 1.0571), socket weld / butt weld160160160250250———

Dimensions:

(mm)DN15DN20DN25DN40DN50DN65DN80DN100
H188188219299299299299299
H1113113133182182182182182
B (EN-JS1049)215215245289289———
B (Steel)217217249292292292292292
B1114114135194194194194194
S180180200300300300300300
S13535506565656565

Socket weld ends (øD / t): DN15: 22 / 10; DN20: 27,3 / 13; DN25: 34 / 13; DN40: 48,9 / 13; DN50: 61,3 / 16. Butt weld ends (øD / s): DN15: 21,3 / 2,0; DN20: 26,9 / 2,3; DN25: 33,7 / 2,6; DN40: 48,3 / 2,6; DN50: 60,3 / 2,9. Other welding end dimensions on request.

Weights (approx.), flanged / screwed sockets / socket weld-butt weld:

(kg)DN15DN20DN25DN40DN50DN65DN80DN100
Fig. 630, flanged8,18,312,129,43032,734,339,2
Fig. 630, screwed sockets7,57,59,724,725,2———
Fig. 630, socket weld / butt weld7,18,110,225,726,7———

Footnotes: 1) DN50 (2”) not in EN-JL/EN-JS. 2) not in EN-JL / EN-JS.

ARI CONA® S Fig. 630 sectional drawing

Parts and Materials

Pos.Sp.p.DescriptionFig. 12.630Fig. 25.630Fig. 45.630Fig. 55.630Fig. 85.630
1BodyEN-JL1040EN-JS10491.04601.45411.0571
11xSealing ringCUA4A4A4A4
16HoodEN-JL1040EN-JS10491.0619+N1.43081.6220+QT
17xGasketGraphite (CrNi laminated with graphite)
24xController, cpl.1.4301
24.2Strainer1.4301
27Cheese head screwA2-701.77091.7709A2-701.7218
46xBlow down valve, cpl.1.4541
49xSealing ringCUA4A4A4A4
50Plug (M14x1,5)1.11811.11811.11811.45411.4541
51xManual air vent valve1.4541
52xUnion for recovery pipe1.4305

L = spare parts. Resistance and fitness must be verified (contact the manufacturer for information, refer to the product overview and resistance list).

Ordering Information

Selection criteria: steam pressure, back pressure, quantity of condensate, flow medium, nominal diameter / pressure, type of connection, material, place of service or kind of steam consumer. Example for order data: ball float steam trap CONA® S, Fig. 630, PN40, DN50, 1.0460/1.0619+N, controller R22, with flanges, face-to-face dimension 230 mm. Other installation positions than standard (vertical) have to be indicated together with the information about the flow direction, i.e. inlet from left or right.

Specify ARI CONA® S Fig. 630, Fig. no. (12.630 / 25.630 / 45.630 / 55.630 / 85.630), DN, PN, controller (R2 to R32), type of connection and quantity when requesting a quotation.